espa
Component Positive plate Raw material Lead dioxide
Negative plate Container Lead ABS
Cover Separator Electrolyte ABS AGM Gel
Safety valve Rubber
Terminal Copper
Constant Current Discharge Characteristics Unit:A(25°C,77°F)
Constant Power Discharge Characteristics Unit:W(25°C,77°F)
F.V/Time
15min
30min
60min
2h
3h
4h
5h
6h
8h
10h
20h
9.60V
400
243
150
91.4
65.0
51.0
43.4
38.3
30.6
25.5
13.5
9.90V
390
238
148
90.8
64.6
50.7
43.1
38.0
30.4
25.4
10.2V
376
230
144
90.0
64.2
50.4
42.8
37.8
30.2
25.3
13.4
10.5V
363
225
140
88.7
63.8
50.0
42.5
37.5
30.0
25.2
13.3
10.8V
344
217
135
86.4
62.5
48.5
41.2
36.4
29.1
25.0
4392
2721
1710
1058
765
600
512
452
364
304
162
4287
2666
1684
1052
760
596
509
449
361
303
4128
2585
1642
1042
755
592
506
446
359
302
161
3988
2522
1590
1027
750
588
502
443
356
301
160
3777
2430
1539
1001
735
570
487
430
346
299
159
Note: The above characteristics data can be obtained within three charge or discharge cycles.
Capacity (25°C)
20HR(10.8V) 3HR(10.8V) 1HR(10.5V)
250Ah
187.5Ah
140Ah
Terminal type
T16
Internal resistance (Fully charged,25°C)
Approx.2.8m Ω
Capacity affected by temperature
(20HR)
40°C
102%
25°C
100%
0°C
85%
-15°C
65%
Self-discharge (25°C)
3 months
Remaining Capacity:91%
6 months
Remaining Capacity:82%
12 months
Remaining Capacity:65%
Nominal operating temperature
25°C±3°C(77°F±5°F)
Operatingtemperature Charge
range
Storage
Discharge
-15°C~50°C(5°F~122°F)
-10°C~50°C(14°F~122°F)
-20°C~50°C(-4°F~122°F)
Float charging voltage(25°C)
13.50 to 13.80V Temperature compensation: -18mV/°C
Cyclic charging voltage(25°C)
14.40 to 14.70V Temperature compensation: -30mV/°C
Maximum charging current
50A
Maximum discharge current
1500A(5 sec.)
Designed floating life(20°C)
12years